2011 Changes to the NEC - 240.21
Based on - NEC - 2011 Edition

2011 Changes to the NEC – 240.21

The following is an instructional page from our 2011 Changes to the NEC Textbook/DVD Package complete with graphics and video where applicable. As part of our on-going effort to provide free resources to help the industry, we will be sending this content as part of a series of newsletters. Each newsletter will feature pages taken directly from our textbooks. This can be a great training resource for your organization!

There are some important features in this text which help to highlight the changes that you should be aware of:

  • Each Code section which contains a change includes a summary of the change, followed by a paraphrase of the NEC text affected by the change. Any specific change is denoted by underlined text and in the corresponding chapter color
  • Graphics with green borders and 2011 CC icons next to the heading are graphics that contain a 2011 change; graphics without a green border or icon are graphics that support the concept being discussed, but nothing in the graphic was affected by a 2011 Code change.
2011 Changes to the NEC Part 1

240.21(B)(1)(4) 10-Foot Feeder Tap

An editorial revision has been made to provisions for sizing a 10 ft feeder tap conductor.


240.21 Overcurrent Protection Location in Circuit.

Except as permitted by (A) through (G), overcurrent devices must be placed at the point where the branch circuit or feeder conductors receive their power. Taps and transformer secondary conductors aren’t permitted to supply another conductor (tapping a tap isn’t permitted).

Image1

Figure 240-7 (Click on image to enlarge)

(B) Feeder Taps. Conductors can be tapped to a feeder as specified in 240.21(B)(1) through (B)(5).

(1) 10-Foot Feeder Tap. Feeder tap conductors up to 10 ft long are permitted without overcurrent protection at the tap location if the tap conductors comply with the following:

(1) The ampacity of the tap conductor must not be less than:

a. The calculated load in accordance with Article 220, and

b. The rating of the device or overcurrent device supplied by the tap conductors.

Image2

Figure 240-8 (Click on image to enlarge)

(2) The tap conductors must not extend beyond the equipment they supply.

(3) The tap conductors are installed in a raceway if they leave the enclosure.

(4) If the tap conductors leave the enclosure or vault in which the tap is made, the tap conductors must have an ampacity not less than 1/10th of the rating of the overcurrent device that protects the feeder.

Note: See 408.36 for the overcurrent protection requirements for panelboards.

Example: A 400A breaker protects a set of 500 kcmil feeder conductors. There are three taps fed from the 500 kcmil feeders that supply disconnects with 200A, 150A, and 30A overcurrent devices. What are the minimum size conductors for these taps?

Image3

Figure 240-9 (Click on image to enlarge)

  • 200A: 3/0 AWG is rated 200A at 75°, and is greater than 10 percent of the ampacity of 500 kcmil, which is rated 380A at 75°.
  • 150A: 1/0 AWG is rated 150A at 75°, and is greater than 10 percent of the ampacity of 500 kcmil, which is rated 380A at 75°.
  • 30A: 8 AWG is rated 50A at 75°, and is greater than 10 percent of the ampacity of 500 kcmil, which is rated 380A at 75°. Anything smaller than 8 AWG can’t be used, as it will have an ampacity of less than 10 percent of 380A (38A) in the 75° column of 310.15(B)(16).
 

ANALYSIS: Previous editions of the Code have required that the overcurrent device upstream of the feeder tap not exceed 10 times the ampacity of the conductor. This revision changes the wording to require that the conductor have an ampacity of not less than 1/10 the rating of the overcurrent device. This results in no technical change whatsoever, but provides a section that’s easier to read. It also brings the NEC text into alignment with the existing text of 240.21(B)(2)(1).

 

2011 NEC Changes DVD Package
Image4

Don't let the scale of the code changes intimidate you, this package will get you up to speed on the most essential 2011 NEC changes quickly. The book is well-organized, easy to follow, and the full-color illustrations bring the material to life. The DVDs bring together a group of experts from the field to discuss the changes and how they apply in the real-world.

This program includes the following items:

  • Changes to the NEC 2011 Textbook
  • Changes to the NEC 2011 DVD 1 & 2 includes Articles 90 - 810

Product Code: 11CCDVD
Price: $198.00

Order Now

 

 
footer
This newsletter was sent to 23565 Subscribers
Comments
    No comments to display

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter