NEC Questions and Answers – Based on the 2011 NEC
October 2011 - Part 1 of 2
By Mike Holt for EC&M Magazine
Here’s the follow up to yesterday’s newsletter. This includes all of the answers to the questions sent, so you can see how you did.
Q1. When adding a ceiling outlet for a new paddle fan in a bedroom, does the Code require this circuit addition to be AFCI protected?
A1. Where branch-circuit wiring is modified, replaced, or extended in any of the areas of a dwelling unit specified in 210.12(A), the branch circuit must be protected by [210.12(B)]:
Q2. Section 220.54 expresses dryer loads in watts and Table 220.55 provides wattage demands for ranges. Can watts be converted to VA for service calculations?
A2. Yes. The feeder/service load for electric clothes dryers located in a dwelling unit must not be less than 5,000W (5,000 VA), or the nameplate rating of the equipment if more than 5,000W (5,000 VA). Kilovolt-amperes (kVA) is considered equivalent to kilowatts (kW) for loads calculated in this section [220.54].
When a building contains five or more dryers, it’s permissible to apply the demand factors listed in Table 220.54 to the total connected dryer load.
Q3. In what rooms of a dwelling unit are switched receptacles allowed to be used for the required lighting outlets?
A3. At least one wall switch-controlled lighting outlet must be installed in every habitable room and bathroom of a dwelling unit [210.70(A)(1)].
Ex 1: In other than kitchens and bathrooms, a receptacle controlled by a wall switch can be used instead of a lighting outlet.
Ex 2: Lighting outlets can be controlled by occupancy sensors equipped with a manual override that permits the sensor to function as a wall switch.
Q4. Does the NEC require that conductors be twisted together before a twist-on wire connector is installed?
A4. Conductors must be spliced by a splicing device identified for the purpose or by exothermic welding [110.14(B)].
Author’s Comment: Conductors aren’t required to be twisted together prior to the installation of a twist-on wire connector, unless specifically required in the installation instructions.
Q5. Are there any requirements for the terminals used for the connection of aluminum conductors?
A5. Conductor terminal and splicing devices must be identified for the conductor material and they must be properly installed and used [110.14].
Connectors and terminals for conductors more finely stranded than Class B and Class C, as shown in Table 10 of Chapter 9, must be identified for the conductor class.
Switches and receptacles marked CO/ALR are designed to ensure a good connection through the use of the larger contact area and compatible materials. The terminal screws are plated with the element called “Indium.” Indium is an extremely soft metal that forms a gas-sealed connection with the aluminum conductor.
Copper and Aluminum Mixed. Copper and aluminum conductors must not make contact with each other in a device unless the device is listed and identified for this purpose.
Note: Many terminations and equipment are marked with a tightening torque, see Table I.1 in Informative Annex I.
Answer: Call the manufacturer, visit the manufacturer’s Website, or have the supplier make a copy of the installation instructions.
Q6. What are the Code requirements for a concrete encased electrode?
A6. A concrete-encased electrode must consist of at least 20 ft of either of the following [250.52(A)(3)]:
(1) One or more of bare, zinc-galvanized, or otherwise electrically conductive steel reinforcing bars of not less than ½ in. diameter, mechanically connected together by steel tie wires, welding, or other effective means, to create a 20 ft or greater length.
(2) Bare copper conductor not smaller than 4 AWG.
The reinforcing bars or bare copper conductor must be encased by at least 2 in. of concrete located horizontally near the bottom of a concrete footing or vertically within a concrete foundation that’s in direct contact with the earth.
If multiple concrete-encased electrodes are present at a building/structure, only one is required to serve as a grounding electrode.
Note: Concrete containing insulation, vapor barriers, films or similar items separating it from the earth isn’t considered to be in “direct contact” with the earth.
Q7. Is an over-counter light in a dwelling unit kitchen allowed to be hardwired to the small-appliance circuit?
A7. Not Supply Other Outlets. The 20A, 120V small-appliance circuits required by 210.11(C)(1) must not supply outlets for luminaires or appliances [210.52(B)(2)].
Ex 1: The 20A, 120V small-appliance branch circuit can be used to supply a receptacle for an electric clock.
Ex 2: A receptacle can be connected to the small-appliance branch circuit to supply a gas-fired range, oven, or counter-mounted cooking unit.
Q8. If you replace a two-wire receptacle with no equipment grounding conductor with a GFCI, is an equipment grounding conductor required for the GFCI?
A8. If no equipment grounding conductor exists in the outlet box for the receptacle, such as old 2-wire Type NM cable without an equipment grounding conductor, existing nongrounding-type receptacles can be replaced using one of the following [406.4(D)(2)]:
(a) Another nongrounding-type receptacle.
(b) A GFCI-type receptacle marked “No Equipment Ground.”
(c) A grounding-type receptacle, if GFCI protected and marked “GFCI Protected” and “No Equipment Ground.”
Caution: The permission to replace nongrounding-type receptacles with GFCI-protected grounding-type receptacles doesn’t apply to new receptacle outlets that extend from an existing outlet box that’s not connected to an equipment grounding conductor. Once you add a receptacle outlet (branch-circuit extension), the receptacle must be of the grounding type and it must have its grounding terminal connected to an equipment grounding conductor of a type recognized in 250.118, in accordance with 250.130(C).
Q9. What is the purpose of grounding electrical systems?
A9. Electrical power systems, such as the secondary winding of a transformer are grounded (connected to the earth) to limit the voltage induced by lightning, line surges, or unintentional contact by higher-voltage lines [250.4(A)(1)].
Note: An important consideration for limiting imposed voltage is to remember that grounding electrode conductors shouldn’t be any longer than necessary and unnecessary bends and loops should be avoided.
Q10. What is the purpose of grounding electrical equipment?
A10. Metal parts of electrical equipment are grounded (connected to the earth) to reduce induced voltage on metal parts from exterior lightning so as to prevent fires from an arc within the building/structure [250.4(A)(2)].
DANGER: Failure to ground the metal parts can result in high voltage on metal parts from an indirect lightning strike to seek a path to the earth within the building—possibly resulting in a fire and/or electric shock.
For more NEC Practice purchase Mike Holt's NEC Practice Questions book, Based on the 2011 NEC. www.MikeHolt.com/NEC