This article was posted 05/24/2011 and is most likely outdated.

Mike Holt Newsletters
 

 

Topic - NEC Questions
Subject - 2011 NEC Questions & Answers - May 2011

May 24, 2011
This newsletter was sent to 17051 newsletter subscribers

Ask a Question |  Continuing EducationQuizzes |  Free Stuff Instructors Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ]  

NEC Questions and Answers – Based on the 2011 NEC
May 2011

By Mike Holt for EC&M Magazine

Here’s the follow up to yesterday’s newsletter. This includes all of the answers to the questions sent, so you can see how you did.

Q1. What are the basic working space requirements for a dwelling unit?

A1. The same rules apply to dwelling units as for any other occupancy.  According to 110.26, access and working space must be provided about all electrical equipment, for the purpose of safe operation and maintenance of equipment.

(A) Working Space. Equipment that may need examination, adjustment, servicing, or maintenance while energized must have working space provided in accordance with (1), (2), and (3):

Author’s Comment: The phrase “while energized” is the root of many debates. As always, check with the AHJ to see what equipment he or she believes needs a clear working space.

(1) Depth of Working Space. The working space, which is measured from the enclosure front, must not be less than the distances contained in Table 110.26(A)(1). For dwelling units, the minimum depth required from this table is 3 ft, since the voltage to ground is not over 150V in dwelling units. 

 (2) Width of Working Space. The width of the working space must be a minimum of 30 in., but in no case less than the width of the equipment.

Author’s Comment: The width of the working space can be measured from left-to-right, from right-to-left, or simply centered on the equipment, and the working space can overlap the working space for other electrical equipment.

In all cases, the working space must be of sufficient width, depth, and height to permit all equipment doors to open 90 degrees.

(3) Height of Working Space (Headroom). The height of the working space in front of equipment must not be less than 6½ ft, measured from the grade, floor, platform, or the equipment height, whichever is greater.

Equipment such as raceways, cables, wireways, cabinets, panels, and so on, can be located above or below electrical equipment, but must not extend more than 6 in. into the equipment’s working space.

Ex 1: The minimum headroom requirement doesn’t apply to service equipment or panelboards rated 200A or less located in an existing dwelling unit.

 

Q2. What are the grounding requirements for a portable generator?

A2. According to 250.34(A), the frame of a portable generator isn’t required to be grounded (connected to the earth) if:

(1) The generator only supplies equipment or receptacles mounted on the generator, and

(2) The metal parts of the generator and the receptacle grounding terminal are connected to the generator frame.

The frame of a vehicle-mounted generator isn’t required to be grounded (connected to the earth) according to 250.34(B) if:

(1) The generator frame is bonded to the vehicle frame,

(2) The generator only supplies equipment or receptacles mounted on the vehicle or generator, and

(3) The metal parts of the generator and the receptacle grounding terminal are connected to the generator frame.

 A portable or vehicle-mounted generator used as a separately derived system to supply equipment or receptacles mounted on the vehicle or generator must have the neutral conductor connected to the generator frame [250.34(C)].

Note: A portable or vehicle-mounted generator supplying fixed wiring for a premises must be grounded (connected to the earth) and bonded in accordance with 250.30 for separately derived systems and 250.35 for nonseparately derived systems.

 

Q3. What are the receptacle spacing requirements for a dwelling unit, in other than kitchens or bathrooms?

A3. Section 210.52 provides requirements for 15A and 20A, 125V receptacle outlets in dwelling units. The receptacles required by this section are in addition to any receptacle that is:

(1) Part of a luminaire or appliance,

(2) Controlled by a wall switch in accordance with 210.70(A)(1), Ex 1.

(3) Located within cabinets or cupboards, or

(4) Located more than 5½ ft above the floor.

(A) General Requirements—Dwelling Unit. A receptacle outlet must be installed in every kitchen, family room, dining room, living room, sunroom, parlor, library, den, bedroom, recreation room, and similar room or area in accordance with (1), (2), and (3):

(1) Receptacle Placement. A receptacle outlet must be installed so that no point along the floor line of any wall is more than 6 ft, measured horizontally along the floor line, from a receptacle outlet.

Author’s Comment: The purpose of this rule is to ensure that a general-purpose receptacle is conveniently located to reduce the chance that an extension cord will be used.

(2) Definition of Wall Space.

(1) Any space 2 ft or more in width, unbroken along the floor line by doorways and similar openings, fireplaces, and fixed cabinets.

(2) The space occupied by fixed panels in exterior walls.

(3) The space occupied by fixed room dividers, such as freestanding bar-type counters or guard rails.

(3) Floor Receptacle Outlets. Floor receptacle outlets aren’t counted as the required receptacle wall outlet if they’re located more than 18 in. from the wall.

(4) Countertop Receptacles. Receptacles installed for countertop surfaces as required by 210.52(C), can’t be used to meet the receptacle requirements for wall space as required by 210.52(A).

Ex 1: The 20A, 120V small-appliance branch circuit can be used to supply a receptacle for an electric clock.

Ex 2: A receptacle can be connected to the small-appliance branch circuit to supply a gas-fired range, oven, or counter-mounted cooking unit.

Author’s Comment: A range hood or above the range microwave listed as a range hood must be supplied by an individual branch circuit [422.16(B)(4)(5)].

 

Q4.  What are the overcurrent protection and conductor sizing requirements for a transformer with a primary voltage of under 600V? Can you give an example for a 45 kVA 480V, three-phase transformer?

A4. Overcurrent Protection for Transformers Not Over 600V is covered by 450.3(B). The primary winding of a transformer must be protected against overcurrent in accordance with the percentages listed in Table 450.3(B) and all applicable notes.

 

Table 450.3(B) Primary Protection Only

 

Primary Current Rating

 

Maximum Protection

 

9A or More

 

125%, see Note 1

 

Less Than 9A

 

167%

 

Less Than 2A

 

300%

 

Note 1. If 125 percent of the primary current doesn’t correspond to a standard rating of a fuse or nonadjustable circuit breaker, the next higher rating is permitted [240.6(A)].

 

Question: What’s the primary overcurrent device rating and conductor size required for a 45 kVA, three-phase, 480V transformer that’s fully loaded? The terminals are rated 75°C.

(a) 8 AWG, 40A                                     (b) 6 AWG, 50A
(c) 6 AWG, 60A                                     (d) 4 AWG, 70A

Answer: (d) 4 AWG, 70A

Step 1:                     Determine the primary current:

I = VA/(E x 1.732)

I = 45,000 VA/(480V x 1.732)

I = 54A

Step 2: Determine the primary overcurrent device rating [240.6(A)]:

54A x 1.25 = 68A, next size up 70A, Table 450.3(B), Note 1

Step 3:         The primary conductor must be sized to carry 54A continuously (54A x 1.25 = 68A) [215.2(A)(1)] and be protected by a 70A overcurrent device [240.4(B)]. A 4 AWG conductor rated 85A at 75°C meets all of the requirements [110.14(C)(1) and 310.15(B)(16)].

 

Q5. Are anti-short bushings required for both Type AC and Type MC Cable terminations?

A5. Type AC cable must terminate in boxes or fittings specifically listed for Type AC cable to protect the conductors from abrasion [300.15 and 320.40].

An insulating anti-short bushing, sometimes called a “redhead,” must be installed at all Type AC cable terminations. The termination fitting must permit the visual inspection of the anti-short bushing once the cable has been installed [320.40].

Author’s Comments:

•  The internal aluminum bonding strip within the cable serves no electrical purpose once outside the cable, and can be cut off, but many electricians use it to secure the anti-short bushing to the cable. See 320.108.

•  Conductors 4 AWG and larger that enter an enclosure must be protected from abrasion during and after installation by a fitting that provides a smooth, rounded, insulating surface, such as an insulating bushing unless the design of the box, fitting, or enclosure provides equivalent protection in accordance with 300.4(G).

Fittings used to secure Type MC cable to boxes or other enclosures must be listed and identified for such use [300.15 and 330.40].

Author’s Comments:

•  The NEC doesn’t require anti-short bushings (red heads) at the termination of Type MC cable, but if they’re supplied it’s considered by many to be a good practice to use them.

•  Conductors 4 AWG and larger that enter an enclosure must be protected from abrasion during and after installation by a fitting that provides a smooth, rounded, insulating surface, such as an insulating bushing unless the design of the box, fitting, or enclosure provides equivalent protection in accordance with 300.4(G).

 

Q6. What are the GFCI protection requirements for a 15 or 20A, 125V receptacle outlet on the dwelling unit laundry circuit?

A6. For other than kitchen sinks, GFCI protection is required for all 15A and 20A, 125V receptacles located within an arc measurement of 6 ft from the outside edge of the sink [210.8(A)(7)]. If the laundry receptacle is located beyond this 6 ft arc, there are no other Code requirements that it be GFCI protected.

 

Q7. Is it allowable to install a cable wiring method inside a circular raceway for a short distance for support or protection?

A7. The general rule covering the mechanical continuity of raceways requires that raceways and cable sheaths must be mechanically continuous between boxes, cabinets, and fittings [300.12].

However, there are exceptions:

Ex 1: Short sections of raceways used to provide support or protection of cable from physical damage aren’t required to be mechanically continuous [250.86 Ex 2 and 300.10 Ex 1].

Ex 2: Raceways at the bottom of open-bottom equipment, such as switchboards, motor control centers, and transformers, aren’t required to be mechanically secured to the equipment.

Author’s Comment: When raceways are stubbed into an open-bottom switchboard, the raceway, including the end fitting, can’t rise more than 3 in. above the bottom of the switchboard enclosure [408.5].

 

Q8. Is it permissible to lengthen the conductors by splicing them inside the panelboard when changing out a service?

A8. Section 312.8 allows cabinets, cutout boxes, and meter socket enclosures to be used for conductors as feeding through, spliced, or tapping off to other enclosures, switches, or overcurrent devices where all of the following conditions are met:

(1) The total area of the conductors at any cross section doesn’t exceed 40 percent of the cross-sectional area of the space.

(2) The total area of conductors, splices, and taps installed at any cross section doesn’t exceed 75 percent of the cross-sectional area of that space.

(3) A warning label on the enclosure identifies the disconnecting means for feed-through conductors.

 

Q9. When low voltage thermostat cable is used for connecting the photo eye used as a sensor to reverse a garage door opener in a commercial occupancy, must it be installed in a raceway?

A9. Only those sections contained in Article 300 specifically referenced in 725.3 apply to Class 1, 2, and 3 circuits [725.3].

Author’s Comment: Boxes or other enclosures aren’t required for Class 2 or Class 3 splices or terminations because Article 725 doesn’t reference 300.15 which contains these requirements.

If installed in a raceway, 725.3(A) requires that the number and size of conductors or cables in a raceway be limited in accordance with 300.17. Raceways must be large enough to permit the installation and removal of conductors without damaging conductor insulation.

Author’s Comment: When all conductors in a raceway are the same size and insulation, the number of conductors permitted can be found in Annex C for the raceway type.

Article 725 does not require that Class 2 or 3 conductors be installed in a Chapter 3 wiring method, such as a raceway.

Equipment and cabling must be installed in a neat and workmanlike manner according to 725.24. Exposed cables must be supported by the structural components of the building so that the cable won’t be damaged by normal building use. Such cables must be secured by straps, staples, hangers, cable ties, or similar fittings designed and installed in a manner that won’t damage the cable.

Author’s Comment: Raceways and cables can be supported by independent support wires attached to the suspended ceiling in accordance with 300.11(A).

In summary, Class 2 and 3 conductors are not required to be installed in a raceway unless it is for protection or if specific requirements of a location, such as a hazardous classified location, would require the use of a raceway.

 

Q10. Are receptacle outlets allowed above a suspended lay-in tile ceiling for cord-connected loads such as temporary holiday lighting displays?

A10. Not if the lighting makes use of flexible cords. According to 400.8(5), flexible cords must not be concealed by walls, floors, or ceilings, or located above suspended or dropped ceilings.

Author’s Comments:

•  Flexible cords are permitted under a raised floor (with removable panels) used for environmental air, because this area isn’t considered a concealed space. See the definition of “Exposed” in Article 100.

•  Receptacles are permitted above a suspended ceiling, but a flexible cord isn’t. Why install a receptacle above a ceiling if the flexible cord isn’t permitted in this space? Because the receptacle can be used for portable tools; it just can’t be used for cord-and-plug-connected equipment fastened in place, such as a projector.

 

Q11. Are communication and computer networking cables required to be listed for use in wet locations per 310.10(C) when installed in an underground raceway as covered by 300.5(B)?

A11. The requirements in 310.10(C) that conductors installed in underground raceways must be listed for wet locations does not apply to underground communications cables entering buildings [800.47]. Remember that communications systems aren’t subject to the general requirements contained in Chapters 1 through 4 or the special requirements of Chapters 5 through 7, except where a Chapter 8 rule specifically refers to one of those chapters [90.3]. Also, installations of communications equipment under the exclusive control of communications utilities located outdoors, or in building spaces used exclusively for such installations, are exempt from the NEC [90.2(B)(4)].

 

Q12. Are 240V receptacles installed in a dwelling unit garage required to have GFCI protection?

A12. GFCI protection for dwelling units is required for all 15A and 20A, 125V receptacles located in the locations listed in 210.8(A), which includes garages and accessory buildings [210.8(A)(2)]. There is no requirement for GFCI protection in these locations for receptacles rated over 125V, such as 240V receptacles.

Author’s Comment: See the definitions of “GFCI” and “Dwelling Unit” in Article 100.

 (2) Garages and Accessory Buildings. GFCI protection is required for all 15A and 20A, 125V receptacles in garages, and in grade-level portions of accessory buildings used for storage or work areas of a dwelling unit.

Author’s Comments:

•  See the definition of “Garage” in Article 100.

•  A receptacle outlet is required in a dwelling unit attached garage [210.52(G)], but a receptacle outlet isn’t required in an accessory building or a detached garage without power. If a 15A or 20A, 125V receptacle is installed in an accessory building, it must be GFCI protected.

 

Q13. Is GFCI protection required for electric hand dryers in a public restroom?

A13. GFCI protection is required for all 15A and 20A, 125V receptacles installed in the “other than dwelling units” locations listed in 210.8(B). This includes the bathroom receptacles mentioned in 210.8(B)(1), but does not include any hard-wired equipment such as hand dryers. Only if the hand dryer is cord and plug connected to a 125V rated 15A or 20A receptacle does it require GFCI protection.

(1) Bathrooms. All 15A and 20A, 125V receptacles installed in commercial or industrial bathrooms must be GFCI protected.

Author’s Comments:

•  See the definition of “Bathroom” in Article 100.

•  A 15A or 20A, 125V receptacle isn’t required in a commercial or industrial bathroom, but if one is installed, it must be GFCI protected.

Q14. Is it acceptable to install communication cable in the same lighting pole which is being used as a raceway for lighting conductors?

A14. Only if there is a barrier or listed divider between the communication cable and the power conductors.

Communications conductors must not be placed in any raceway, compartment, outlet box, junction box, or similar fitting with conductors of electric light, power or Class 1 circuits [800.133(A)(1)(d)].  

Ex 1: Communications circuits can be within the same enclosure with conductors of electric light, power and Class 1 circuits, where separated by a permanent barrier or listed divider.

Author’s Comment: Separation is required to prevent a fire or shock hazard that can occur from a short between the communications circuits and the higher-voltage circuits.

 

Q15. In a commercial occupancy, does the Code require that each office must have its own separate light switch to control the luminaires in that office?

A15. In non-dwelling locations, the installation of light switches is not generally specified by the Code, although 210.70(C) addresses the requirements for switches to control lighting where the illumination is needed to service equipment.

(C) Other Than Dwelling Units. At least one lighting outlet that contains a switch or is controlled by a wall switch must be installed in attics and underfloor spaces containing equipment that requires servicing. The switch must be located at the usual point of entry to these spaces, and the lighting outlet must be located at or near the equipment requiring servicing.

Author’s Comment: A 15A or 20A, 125V receptacle must be installed within 25 ft of HACR equipment [210.63].

In dwelling units, there are more specific requirements in regard to lighting outlets and switch control for them:

210.70 Lighting Outlet Requirements.

(A) Dwelling Unit Lighting Outlets. Lighting outlets must be installed in:

(1) Habitable Rooms. At least one wall switch-controlled lighting outlet must be installed in every habitable room and bathroom of a dwelling unit.

Author’s Comment: See the definition of “Lighting Outlet” in Article 100.

Ex 1: In other than kitchens and bathrooms, a receptacle controlled by a wall switch can be used instead of a lighting outlet.

Ex 2: Lighting outlets can be controlled by occupancy sensors equipped with a manual override that permits the sensor to function as a wall switch.

Author’s Comment: The Code specifies the location of the wall switch-controlled lighting outlet, but it doesn’t specify the switch location. Naturally, you wouldn’t want to install a switch behind a door or other inconvenient location, but the NEC doesn’t require you to relocate the switch to suit the swing of the door. When in doubt as to the best location to place a light switch, consult the job plans or ask the customer.

(2) Other Areas.

(a) Hallways, Stairways, and Garages. In dwelling units, not less than one wall switch-controlled lighting outlet must be installed in hallways, stairways, attached garages, and detached garages with electric power.

(b) Exterior Entrances. At least one wall switch-controlled lighting outlet must provide illumination on the exterior side of outdoor entrances or exits of dwelling units with grade-level access.

Author’s Comments:

•  The NEC doesn’t require a switch adjacent to each outdoor entrance or exit. The Code considers switch location a “design issue” which is beyond the purpose of the NEC [90.1(C)]. For this reason, proposals to mandate switch locations have been rejected.

•  A lighting outlet isn’t required to provide illumination on the exterior side of outdoor entrances or exits for a commercial or industrial occupancy.

(c) Stairway. If the stairway between floor levels has six risers or more, a wall switch must be located at each floor level and at each landing level that includes an entryway to control the illumination for the stairway.

Ex to (a), (b), and (c): Lighting outlets for hallways, stairways, and outdoor entrances can be switched by a remote, central, or automatic control device.

(3) Storage and Equipment Rooms. At least one lighting outlet that contains a switch or is controlled by a wall switch must be installed in attics, underfloor spaces, utility rooms, and basements used for storage or containing equipment that requires servicing. The switch must be located at the usual point of entry to these spaces, and the lighting outlet must be located at or near the equipment that requires servicing.

(B) Guest Rooms or Guest Suites. At least one wall switch-controlled lighting outlet must be installed in every habitable room and bathroom of a guest room or guest suite of hotels, motels, and similar occupancies.

Ex 1: In other than bathrooms and kitchens, a receptacle controlled by a wall switch is permitted in lieu of lighting outlets.

Ex 2: Lighting outlets can be controlled by occupancy sensors equipped with a manual override that permits the sensor to function as a wall switch.

 

 

 

Click here to post a comment

[ Post Your Comments | View Comments | Notify Me When Comments Are Added ]
[ View More Newsletters ]

Bookmark and Share


Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

 

 
Comments
  • Q10. According to 400.8(5) flexible cords must not be... located above suspended or dropped ceilings.

    While flexible cords are not typically plenum rated, there are now manufacturers of plenum rated power cords such as could be used to supply power to a ceiling mounted audiovisual projector. But the Article here does seem to exempt flexible plenum rated power cords. Thoughts?

    Tom Kehr  May 25 2011, 2:35 pm EDT
    Reply to this comment

  • Q15. In a commercial occupancy, does the Code require that each office must have its own separate light switch to control the luminaires in that office?

    NFPA-70 may not; but be aware that another code may go well beyond simply requiring a 'switch'.

    Where adopted, ASHRAE/IES 90.1-2010 now requires: • automatic shutoff of indoor and outdoor lighting when not in use, for all buildings <5,000 sq.ft. unless specifically exempted

    • automatic shutoff must be added alongside any "lamp+ballast" retrofits of >10% of the connected lighting load;

    • occupancy sensors are required for a large list of applications, INCLUDING OFFICE areas up to 250 sf

    • manual-ON or auto-ON to 50% operation required for all of the above automatic controls

    • multilevel lighting in spaces using manual space controls, including offices

    • automatic multilevel lighting in some areas including stairwells and parking

    • may even run into some automatic daylight harvesting controls as this is becoming standard practice

    RSanders  May 25 2011, 11:15 am EDT
    Reply to this comment

  • Concerning Q10: While holiday lighting may not fall under the under that first statement of 400.8 that reads "Unless specifically permitted in 400.7 . . . " since they may not be considered "Wiring of luminaires" that is allowed by 400.7 there are other things, like projectors, that seem to be allowed by item (6) or (8) of 400.7. Most code authorities seem to ignore the statement at the beginning of 400.8 about unless being allowed by 400.7. What purpose does the statement at the beginning of 400.7 serve if it doesn't allow a projector be cord and plug connected throught the ceiling?

    John  May 25 2011, 8:47 am EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter