Grounding and Bonding

250.8 Termination of Grounding and Bonding Conductors

Revised text clarifies that terminals for grounding conductors or bonding jumpers must be attached to enclosures in a suitable method to ensure an effective ground-fault path.

The termination of equipment grounding and bonding conductors must be by exothermic welding, listed pressure connectors of the set screw or compression type, listed clamps, or other listed fittings. Sheet-metal screws cannot be used to connect grounding (or bonding) conductors or connection devices to enclosures. Figure 250-6

Author’s Comment: The rule still doesn’t prohibit drywall screws or wood screws for being used for this purpose, just “sheet-metal” screws!



Figure 250-6
(Click on image to enlarge)

       
 

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • Hello, I have a question about the ground wires in the time clock. It is my understanding that the clock itself needs to be grounded. In the picture being that it does not bolt in and just clips in. So what i'm asking doesn't the two grounds need to be made together, not separate like they are?

    Boyd

Reply to this comment