This article was posted 07/28/2010 and is most likely outdated.

Determining the Cause of AFCI Tripping
 

 

Topic - Safety
Subject - Determining the Cause of AFCI Tripping

28, 2010
This newsletter was sent to 18967 newsletter subscribers

Ask a Question |  Continuing EducationQuizzes |  Free Stuff Instructors Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ]  

Determining the Cause of AFCI Tripping
Image1

When an AFCI trips, the cause of the trip must be determined before placing the circuit back into service.

Schneider Electric has posted a Data Bulletin on their website that outlines several of the most common causes of AFCI tripping. Written in December 2007, it does not cover all possible causes that can occur, but is one of the more comprehensive troubleshooting guides out there.

Click here or on the image to read or download the document (439.3 Kb)

Visit the Schneider Electric website.

Thanks to Ed Lethert for letting us know about this important document!

 

Click here to post a comment

[ Post Your Comments | View Comments | Notify Me When Comments Are Added ]
[ View More Newsletters ]

Bookmark and Share


Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

 

 
Comments
  • The AFCI is one of the worst examples of manufacturers lobbyists corrupting the NEC code. This is also the reason why we now have to have smoke and CO2 alarms both inside and outside of every bedroom as well as on every floor. I am still waiting to see homeowners insurance go down as a result of this major extra cost in safety devices, but no: The insurance companies will keep the saving on claims to themselves.

    There is one way to avoid AFCIs in new construction, that might be break-even or better in cost: Build the whole thing in EMT. If I were building a house right now, I would certainly do that.

    Paul Dent
    Reply to this comment

  • I thought a kilohm was one thousand ohms. And if that's true, 120 volts divided by one thousand ohms equals 0.120 amps. Most loads draw more current than that. So why is this "less than one kilohm" (on page 2) considered to be low resistance?

    Ralph Greene
    Reply to this comment

  • Everything in this makes perfect sense ... except on page 5, where they say "NOTE: Some electrical equipment such as motors, power converters, etc. may give the appearance of a ground fault, due to normal, non-linear behavior. But usually this leakage is much less than the 50 mA level, especially for devices found in a bedroom." UL puts an upper limit of 3.5 mA (or 5 mA if marked "high leakage current") on leakage current in devices with a grounding power plug. For devices with 2-prong power plugs, the limit is 0.75 mA. What kind of household device can they be referring to?

    Bill Whitlock
    Reply to this comment
  • Reply from: Paul Dent   
    There is very sad situation regarding leakage current. The very common and "UL approved" power lead connector socket for all PC's and displays and many other appiances such as VCRs and other electrical equipment, containes RFI filtering comprising a capacitor from hot to ground/case and a capactitor from neutral to ground. What this means is, if you lose the ground, you get a capacitive potential divider that puts 120volts/2 on to the case of the appliance. It also means there is continuous ground current from such appliances and the total for a whole household or a lab-bench can be significant. I have measured 50mA, which is well into the potentially fatal region. I heard this happened with a piece of hospital equipment conencted to a paralyzed patient via a catheter, and they didn't notice he was in agony for days. When working as an electronic engineer in Europe, where the case rises to 240/2 volts if you lose the ground, I often got a shock when disconnecting a BNC cable linking two pieces of equipment, where the ground had come off one and not the other. I know of a case too where a chip foundry used a wafer tester that operated between 0 and -5v due to the polarity of the substrates they were testing. One time, somebody wanted to connect an HP logic analyzer in to do some manual tests, and the HP analyzer operated from 0 to +5v. So they took the ground off to float it. Upon connecting the two together, the leakage current blew up a $500,000 wafer tester.

    We need this connector to be replaced by a safe one. It is amazing that this issue has been hidden for so long. The correct and safe RFI circuit is one which has the capacitors connected from hot to neutral and from neutral to ground. That way you have to lose both neutral and ground before the case becomes live; and there is no ground leakage current normally. We need much tougher standards on leakage curent. I estimate that, in the US, we are wasting 50 megawatts continuously to warm the earthworms. I would say a good standard would be a current level you can't feel, and that means less than 1mA.

    There was a fatal case involving the same phenomenon at high power. A group of mineworkers were asked to connect power-factor correction capacitors to the 13200 volt lines feeding the winding gear. They connected them in Y-configuration from the three hots to ground. With good phase balance, the ground current should be zero, but one of the capacitors became disconnected, shoving a bunch of imbalance current into the ground rod which only had a resistance of 180 ohms. This raised the local ground system to about 300 volts, killing a worker using an electric drill nearby.

    Moral of the story is: Never connect capacitors from hot to ground: Only from hot to neutral, hot to hot or neutral to ground.
    Reply to Paul Dent


  • Yes I agree thank you Schnieder Electric for posting Square D trouble shooting for AFCI tripping. I only have one question: On Fig. 4 illustration "Shared Neutral" connections circuit 1's second duplex is fed through /from circuit 1's first device in "j"-box. Isn't that a no-no?

    Michael Bennett
    Reply to this comment

  • I have run into AFCI tripping due to operation of capacitor banks on the utility system. The AFCI units were sensitive to the transients created when energizing the cap banks. Brought the issue back to the manufacturer and found out it was a design issue and he supplied replacements to all the homeowners.

    greg t
    Reply to this comment

  • Like that equal potential $1200 bonding grid that "had" to go around a pool a couple years back, I hope someone rethinks about these AFCI's.

    Rich Perrotta
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter