This article was posted 09/01/2006 and is most likely outdated.

Grounding vs Bonding: 250.142 Use of Grounded Neutral Conductor for Equipment Grounding (Bonding)
 

 
Subject - Grounding vs Bonding: 250.142 Use of Grounded Neutral Conductor for Equipment Grounding (Bonding)

September 1, 2006  

| Ask a Question |  Code Graphic Code Quiz - All New! |  Free Stuff Instructors | Feedback
Online Training Products | Seminars | SubscribeUnsubscribe |
Change Email Address |
[ image1 Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

PART VII.   Hi Res - Cable/DSL [1514Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
Sections

250.142 Use of Grounded Neutral Conductor for Equipment Grounding (Bonding).

Author’s Comment: To remove dangerous voltage on metal parts from a ground fault, the metal parts of electrical raceways, cables, enclosures, and equipment must be bonded to an effective ground-fault current path in accordance with 250.4(A)(3).
(A) Supply Side of Service Equipment. A grounded neutral conductor can be used as the effective ground-fault current path for metal parts of equipment, raceways, and other enclosures.

(1) Service Equipment. Because an equipment grounding (bonding) conductor isn’t run from the utility to electrical services, the grounded neutral service conductor can serve as the effective ground-fault current path to the utility power source. Figure 250–183

Author’s Comment: The effective ground-fault current path for service equipment is provided by the installation of the main bonding jumper at service equipment in accordance with 250.24(B) [250.28]. Figure 250–184
(2) Separate Buildings and Structures. Where no equipment grounding (bonding) conductor is run to a building or structure disconnect, the grounded neutral conductor can serve as the effective ground-fault current path to the power source.

Author’s Comment: This is accomplished by bonding the grounded neutral conductor to the equipment grounding (bonding) conductor at the separate building or structure building disconnecting means in accordance with 250.32(B)(2).

CAUTION: Using the grounded neutral conductor as the effective ground-fault current path poses potentially dangerous consequences and should only be done after careful consideration.

Author’s Comment: The safest practice is to install an equipment grounding (bonding) conductor with the feeder conductors to the building or structure to serve as the effective ground-fault current path, as provided by 250.32(B)(1).
(3) Separately Derived Systems. The effective ground-fault current path is established for a separately derived system when the system bonding jumper is installed between the metal enclosure of the separately derived system and the grounded neutral terminal in accordance with 250.30(A)(1).

DANGER: Failure to install the system bonding jumper as required by 250.30(A)(1) will create a condition where dangerous touch voltage from a ground fault will remain on the metal parts of electrical equipment.
(B) Load-Side Equipment. To prevent dangerous voltage on metal parts, the grounded neutral conductor must not be bonded to the equipment grounding (bonding) conductor on the load side of service equipment, except as permitted by 250.142(A).

Exception 1: The grounded neutral conductor can serve as the effective ground-fault current path for existing ranges, dryers, and ovens [250.140 Ex].

Exception 2: The grounded neutral conductor can be bonded to the meter enclosure on the load side of the service disconnecting means if:
Figure 250–185

(a) No service ground-fault protection is installed,

(b) Meter enclosures are located immediately adjacent to the service disconnecting means, and

(c) The grounded neutral conductor is sized not smaller than specified in Table 250.122.



Figure 250–183
(Click on image to enlarge)


Figure 250–184
(Click on image to enlarge)


Figure 250–185
(Click on image to enlarge)

   

[ View More Newsletters ] [ Send to a Friend ] [ Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © 2002, 2003, 2004, 2005, 2006 Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

To suggest a topic or submit content for a newsletter: nlsuggest@mikeholt.com
Experiencing a Problem? Contact our Webmaster

Comments

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter