This article was posted 11/07/2011 and is most likely outdated.

Mike Holt Newsletters
 

 

Topic - NEC
Subject - Disconnect Requirements for Articles 422 through 450 – Based on the 2011 NEC

November 7, 2011
This newsletter was sent to 18169 newsletter subscribers

Ask a Question |  Continuing EducationQuizzes |  Free Stuff Instructors Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ]  

Disconnect Requirements for Articles 422 through 450 – Based on the 2011 NEC

 

By Mike Holt for EC&M

Article 422 covers electric appliances used in any occupancy.

Most NEC articles include definitions unique to that article in a dedicated subsection with the .2 ending. Until the 2011 revision, Article 422 didn’t have such a section and provided the definition for “vending machine” in 422.51. That definition is now in the new Section 422.2.

With the 2011 revision, each appliance must have a means to simultaneously disconnect all ungrounded circuit conductors [422.30]. The NEC has long required appliances to have a means to disconnect the ungrounded conductors supplying them, just not simultaneously. This change helps coordinate this requirement with the provisions of 240.15.

That’s not the only disconnect-related change in Article 422. How you apply the requirements of 422.31 depends on the VA rating and horsepower rating of the appliance. The horsepower rating is actually for the motor of the appliance, yet it raises a concern.

Article 430 requires motors to have a lockable disconnect within sight. What if a lockable disconnect isn’t within sight of a motor-driven appliance? That used to be a confusing aspect of Article 422. The 2011 NEC clarifies that the branch circuit overcurrent device can serve as the disconnect for appliances (if they are not over 300VA or 1/8 horsepower).

Another source of confusion has been in applying the requirements of 422.32 which pertained only to motor-driven appliances, and differed from those in 422.31. In the 2011 Code, 422.32 is gone. A new subsection 422.31(C) exists for appliances rated over 1⁄8 horsepower (motor driven) and 422.31(B) now addresses appliances rated over 300 VA.

In the 2011 NEC revision of 422.31 addresses the disconnection of permanently connected appliances in the following subsections:

  • Subsection (A) applies to nonmotor-operated appliances not over 300VA and motor-operated appliances less than 1⁄8 horsepower.
  • Subsection (B) applies to nonmotor-operated appliances of greater than 300VA.
  • Subsection (C) applies to motor-operated appliances greater than 1⁄8 horsepower.
  • The exception formerly found in 422.32 now applies to 422.31(C).

Fixed space heaters

Has the sheer number of pages in Article 424 ever struck you as a bit “over the top?” This is a nine-part article on fixed electric space heaters. Why so much text for what seems to be a simple application?

The answer is that heaters come in many configurations for various uses, and Article 424 covers them all. Not all of this article applies to electricians in the field though, because Part IV is for manufacturers.

Fixed space heaters (wall-mounted, ceiling-mounted, or free-standing) are common in utility buildings and other small structures, plus in some larger structures. When used to heat floors, space-heating cables help solve the thermal layering problem typical of forced-air systems—so they are in widespread use. Duct heaters commonly provide a distributed heating scheme in large office and educational buildings. Locating the heater in the ductwork close to the occupied space eliminates the waste of transporting heated air through sheet metal ductwork routed in unheated spaces.

The motors for fixed electric space-heaters are now considered a continuous load [424.3(B)]. So size the branch circuit at 125 percent.

GFCI

The NEC has long required GFCI protection of electric space heating cables that heat floors in bathrooms and hydromassage locations. Now this requirement also includes kitchen floors [424.44(G)].

Motors

Article 430 (see Sidebar) didn’t change very much in the 2011 NEC. But there was a change in the requirements for cord-and-plug-connected motors.

While portable motors typically plug into receptacles, often they’re connected to the cord connector of a pendant cord or a flanged surface inlet. Though 210.50(A) addresses cord connectors attached to a pendant cord, 430.109(F) now addresses these also.

For a motor disconnecting means, you can use any of the following if they have a horsepower rating not less than the motor rating:

  • Horsepower-rated attachment plug and receptacle.
  • Flanged surface inlet and cord connector.
  • Attachment plug and cord connector.

Air conditioning and refrigeration equipment

Article 440 includes some changes for air conditioners, beginning with cord-connected room air conditioners. It’s similar to the change we just looked at in Article 430. While cord-and-plug-connected room air conditioners typically plug into receptacles, often they’re connected to the cord connector of a pendant cord. While 210.50(A) addresses this type of installation, 440.63 has now been revised to include such situations.

An attachment plug and receptacle or cord connector can serve as the disconnecting means for a room air conditioner, provided:

(1)        The manual controls on the room air conditioner are readily accessible and within 6 ft of the floor, or

(2)        A readily accessible disconnecting means is within sight from the room air conditioner.

Generators

Generators are basically motors that operate in reverse—they produce electricity when rotated, instead of rotating when supplied with electricity. Article 430, which covers motors, is the longest article in the NEC. Article 445, which covers generators, is one of the shortest. At first, this might not seem to make sense. But you don’t need to size and protect conductors to a generator. You do need to size and protect them to a motor.

Generators need overload protection, and it’s necessary to size the conductors that come from the generator. But these considerations are more straightforward than the equivalent considerations for motors.

The Scope section for Article 445 has been revised to be more accurate. Previously, it said, “This article covers the installation of generators.” Now it says, “This article contains installation and other requirements for generators.” [445.1]

While Article 445 does cover the installation of generators, it also covers the location, marking, overcurrent protection, internal bushing requirements, terminal housings, and disconnecting means for generators. Plus it covers the ampacity of conductors from the generator terminal to the first disconnecting means with overcurrent protection. Instead of including this long list of items, the Code-Making Panel decided to shorten it by stating that Article 445 covers “installation and other requirements” for generators.

Generators, associated wiring, and equipment must be installed in accordance with the following requirements, depending on their use:

•           Article 695, Fire Pumps

•           Article 700, Emergency Systems

•           Article 701, Legally Required Standby Systems

•           Article 702, Optional Standby Systems

Transformers

Article 450 opens by saying, “This article covers the installation of all transformers.” Then it lists eight exceptions. So what does Article 450 really cover? Essentially, it covers power transformers and most kinds of lighting transformers.

The prevention of overheating is a major concern with transformers. The NEC doesn’t completely address this issue, because the NEC isn’t a design manual [90.1(C)].

Proper transformer selection, which the NEC doesn’t address, is an important part of preventing transformer overheating. You need to select a transformer suitable for the load characteristics, the application, and the environment.

Once you’ve done that, Article 450 takes you through the next logical steps—providing overcurrent protection, making the proper connections, meeting ventilation requirements, and allowing for accessibility.

  • Part I contains the general requirements such as guarding, marking, and accessibility.
  • Part II contains the specific provisions for different types of transformers.
  • Part III covers transformer vaults.

Article 450 doesn’t go into acceptance testing or maintenance. For those, you’ll need to refer to other standards.

Disconnecting means

A new section, 450.14, requires a disconnecting means for most transformers. In previous NEC editions, transformers didn’t require a disconnecting means. Although there were no documented injuries to warrant this change, it’s obvious that this requirement should enhance safety.

For transformers other than Class 2 and Class 3, you must provide a means to disconnect all transformer ungrounded primary conductors. The disconnecting means must be within sight of the transformer unless the location of the disconnect is field-marked on the transformer and the disconnect is lockable.

Disconnecting

We just ran through an overview of changes to eight NEC articles. We were able to do that in so little space because the changes weren’t extensive. Did you notice a recurring theme, here? The 2011 NEC requires disconnects where previously they weren’t required.

Adding more disconnects will slightly increase construction costs if they were not already included by designers. But, in addition to the safety benefits, reduced maintenance costs will provide savings to offset the increased construction costs . This is why engineering best practices required disconnects even where the NEC previously did not.

 

Sidebar: Article 430 Issues

Because Article 430 is so large, code users sometimes feel overwhelmed by it. The solution to that problem is to proceed methodically through your motor system installation using Figure 430.1. This illustration gives a good graphical representation of which Parts of Article 430 apply to which parts of the motor system.

A second issue involves sizing the motor branch circuit overcurrent protection. Remember, an overload isn’t the same thing as a short-circuit or ground fault. The fuse or circuit breaker protects the motor branch circuit against short circuits or ground faults, but it is sized large enough to allow the motor to draw the additional current needed for start-up [430.52]. By sizing the branch circuit short circuit and ground fault protection device this large, it will not provide overload protection for the motor. That’s why separate motor overload protection is required [430.32(A)(1)]. This makes overcurrent protection for motor applications necessarily different from the protection employed for other types of equipment. So don’t confuse general overcurrent protection with motor protection - you must calculate and apply them differently using the rules in Article 430.

Image

 

 

Taken from Mike Holt’s 2011 Understanding the NEC Volume 1 Textbook. To order your copy, please click here, or call 888-632-2633

 

 

Click here to post a comment

[ Post Your Comments | View Comments | Notify Me When Comments Are Added ]
[ View More Newsletters ]

Bookmark and Share


Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

 

 
Comments
  • once again mike great information given in an easy to understand fashion! i recently had an argument/disagreement with my boss over motor protection using inverse time circuit breakers. we changed the motor branch circuit feed from a buss plug with dual element fuses to an inverse time circuit breaker ( 175% to 250%). i said we needed to upsize the existing conduit and wire going from bucket/breaker to motor disconnect due to sizing breaker larger to meet 250% requirement and he said we could use same wire due to motor overload protection. i think i am right because the breaker is for short circuit,ground fault protection not overload protection and the wire size is determined by the breaker size not the motor overload protection.

    chris huckins  December 5 2011, 6:28 pm EST
    Reply to this comment

  • Good concise Article Mike, thnak you for your effort.

    Ron Elliott  November 10 2011, 8:50 am EST
    Reply to this comment

  • 408.36 requires a disconnecting means in a panel board or on the supply side conductors. Does this mean in sight of the psnelboard? I can't seem to find the old six movements of the hand to disconnect the panel. I have also seen 4 panels, 1 on 4 different levels, with feed thru lugs, daisy chained from floor to floor and no means to disconnect on each level. Note, the panels at least 16 circuits in each, and all have single pole breakers installed. In both of these cases the overcurrent protection is located in another location in the building and non of these panels are labeled with that location. I need verification. Thanks.

    John Wilson  November 8 2011, 5:05 am EST
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter